Wires & Cables


Southwire

CSA HVTC 5kV Tray Cables

More Products


HVTC CU 3C 115TRXLPE TS PVC 5KV 133% CSA B44

CSA Approvals

  • TC-ER – Tray Cable – Exposed Run rating
  • C22.2 No. 230 – Tray Cable Standard
  • C68.10 MV Shielded Power Cable Standard
  • SUN RES. - Sunlight Resistant
  • FT4 Flame Test
  • -40ºC low temperature rating
  • +105ºC high temperature rating

Designed for harsh Canadian environments

Applications

Southwire's 5KV HVTC is a CSA approved copper tape shielded cable for Industrial and Commercial medium voltage applications. FT4, -40°C, and 105°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. For use in cable trays, exposed run and hazardous locations as per the limitations in the Canadian Electrical Code Part I, particularly Table 19.

Construction

Conductor

  • Class B compressed stranded copper
    - in accordance with ASTM 83 and ASTM B8

Options

  • Class B compact stranded 8000 Series Aluminum -ACM
  • Class B compact stranded copper

Conductor Shield

  • Extruded semi-conducting thermosetting polymeric layer

Insulation

  • TR-XLPE - (Tree Retardant Cross Linked Polyethylene)
  • Thickness: 0.115 inches (2.92mm) - nominal
  • Insulation level: 133%
  • 105°C rated

Insulation Shield

  • Extruded Semi-conducting thermosetting polymeric layer
  • CSA 68.10 - Shield Removal/termination requirements are printed on the surface
  • Phase identification as per ICEA Method 3, using printed circuit numbers
  • Meets requirement of ICEA but built to CSA standards

Copper Tape Shield

  • Helically wrapped 5 mil copper tape with 25% overlap

Bonding Conductor

  • Class B compressed stranded bare copper
    - in accordance with ASTM B3 and B8

Fillers

  • Non-wicking, non-hygroscopic

Overall Jacket

  • Orange PVC (optional colours available)
  • Nominal Thickness:
    No.2 AWG to No.1 AWG = 0.08 inches (2.03mm)
    No.1/0 AWG to 350 kcmil = 0.11 inches (2.79mm)
    500 kcmil to 1000 kcmil = 0.14 inches (3.56mm)

Typical Print Legend

  • (CSA) SOUTHWIRE1NESCHP§ 3/0 [#AWG or #kcmil] CU 115
    TRXLPE 5KV 133% INS LEVEL 25% TS SUN RES TC-ER 105° FT4
    (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]

HVTC AL 3C 90TRXLPE TS PVC 5KV 100% CSA Y75

CSA Approvals

  • TC-ER – Tray Cable – Exposed Run rating
  • C22.2 No. 230 – Tray Cable Standard
  • C68.10 MV Shielded Power Cable Standard
  • SUN RES. - Sunlight Resistant
  • FT4 Flame Test
  • -40ºC low temperature rating
  • +105ºC high temperature rating

Designed for harsh Canadian environments

Applications

Southwire's 5KV HVTC is a CSA approved copper tape shielded cable for Industrial and Commercial medium voltage applications. FT4, -40°C, and 105°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. For use in cable trays, exposed run and hazardous locations as per the limitations in the Canadian Electrical Code Part I, particularly Table 19.

Construction

Conductor

  • Class B - compact stranded -8000 Series Aluminum -ACM

Options

  • Class B compact stranded copper
  • Class B compressed stranded copper
  • Strand blocking technology
  • Tinning on copper conductors

Conductor Shield

  • Extruded semi-conducting thermosetting polymeric layer

Insulation

  • TR-XLPE - [Tree Retardant Cross Linked Polyethylene)
  • Thickness: 0.09 inches (2.29mm) - nominal
  • Insulation level: 100% — grounded system
  • 105°C rated

Insulation Shield

  • Extruded Semi-conducting thermosetting polymeric layer
  • CSA 68.10 - Shield Removal/termination requirements are printed on the surface
  • Phase identification as per ICEA Method 3, using printed circuit numbers
  • Meets requirement of ICEA but built to CSA standards

Copper Tape Shield

  • Helically wrapped 5 mil copper tape with 25% overlap

Bonding Conductor

  • Class B compressed stranded bare copper
    - in accordance with ASTM B3 and B8

Fillers

  • Non-wicking, non-hygroscopic

Overall Jacket

  • Orange PVC (optional colours available)
  • Nominal Thickness:
    No.2 AWG to No.2/0 AWG = 0.08 inches (2.03mm)
    No.3/0 AWG to 500 kcmil = 0.11 inches (2.79mm)
    750 kcmil to 1000 kcmil = 0.14 inches (3.56mm)

Typical Print Legend

  • (CSA) SOUTHWIRE1NESC)#P# 3/C [#AWG or #kcmil] CPT AL 90
    THXLPE SKV 100% INS LEVEL 25% TS SUN RES TC-ER 105° FT4
    (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]

HVTC AL 3c 90EPR TS PVC 5KV 100% CSA X77

CSA Approvals

  • TC-ER – Tray Cable – Exposed Run rating
  • C22.2 No. 230 – Tray Cable Standard
  • C68.10 MV Shielded Power Cable Standard
  • SUN RES. - Sunlight Resistant
  • FT4 Flame Test
  • -40ºC low temperature rating
  • +105ºC high temperature rating

Designed for harsh Canadian environments

Applications

Southwire's 5KV HVTC is a CSA approved copper tape shielded cable for Industrial and Commercial medium voltage applications. FT4, -40°C, and 105°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. For use in cable trays, exposed run and hazardous locations as per the limitations in the Canadian Electrical Code Part I, particularly Table 19.

Construction

Conductor

  • Class B - compact stranded -8000 Series Aluminum -ACM

Options

  • Class B compact stranded copper
  • Class B compressed stranded copper
  • Strand blocking technology
  • Tinning on copper conductors

Conductor Shield

  • Extruded semi-conducting thermosetting polymeric layer

Insulation

  • No-lead EPR (Ethylene Propylene Rubber)
  • Thickness: 0.09 inches (2.29mm) - nominal
  • Insulation level: 100% — grounded system
  • 105°C rated

Insulation Shield

  • Extruded Semi-conducting thermosetting polymeric layer
  • CSA 68.10 - Shield Removal/termination requirements are printed on the surface
  • Phase identification as per ICEA Method 3, using printed circuit numbers
  • Meets requirement of ICEA but built to CSA standards

Copper Tape Shield

  • Helically wrapped 5 mil copper tape with 25% overlap

Bonding Conductor

  • Class B compressed stranded bare copper
    - in accordance with ASTM B3 and B8

Fillers

  • Non-wicking, non-hygroscopic

Overall Jacket

  • Orange PVC (optional colours available)
  • Nominal Thickness:
    No.2 AWG to No.2/0 AWG = 0.08 inches (2.03mm)
    No.3/0 AWG to 500 kcmil = 0.11 inches (2.79mm)
    750 kcmil to 1000 kcmil = 0.14 inches (3.56mm)

Typical Print Legend

  • (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 90 EPH SKV 100% INS LEVEL 25% TS SUN HES TC-EH 105° Fl' 4 (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]

More Products


CSA HVTC 8kV Tray Cables

More Products


HVTC AL 1C 115EPR TS PVC 8KV 100% CSA U38

Product Highlights

Southwire's 5KV HVTC is a CSA approved copper tape shielded cable for Industrial and Commercial medium voltage applications. FT4, -40°C, and 105°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. For use in cable trays, exposed run and hazardous locations as per the limitations in the Canadian Electrical Code Part I, particularly Table 19.

Construction

Conductor

  • Class B - compact stranded -8000 Series Aluminum -ACM

Options

  • Class B compact stranded copper
  • Class B compressed stranded copper
  • Strand blocking technology
  • Tinning on copper conductors

Conductor Shield

  • Extruded semi-conducting thermosetting polymeric layer

Insulation

  • No-lead EPR (Ethylene Propylene Rubber)
  • Thickness: 0.115 inches (2.92mm) - nominal
  • Insulation level: 100% - grounded system
  • 105°C rated

Insulation Shield

  • Extruded Semi-conducting thermosetting polymeric layer
  • CSA 68.10 - Shield Removal/termination requirements are printed on the surface
  • Meets requirement of ICEA but built to CSA standards

Copper Tape Shield

  • Helically wrapped 5 mil copper tape with 25% overlap
  • Not designed to carry ground fault current
  • A separate bonding/grounding conductor may be required

Overall Jacket

  • Black PVC (optional colours available)
  • Nominal Thickness:
    No.2 AWG to No.1/0 AWG = 0.06 inches (1.52mm)
    No.2/0 AWG to 1000 kcmil = 0.08 inches (2.03mm)

Typical Print Legend

  • (CSA) SOUTHWIRE (NESC) #P# [#AWG or #kcmil] CPT ALL 115 EPR
    8KV 100% INS LEVEL 25% TS SUN RES TC-ER 105° FT4 (-40°C)
    LTGG RoHS YEAR [SEQUENTIAL METER MARKS]

HVTC AL 1C 115TRXLPE TS PVC 8KV 100% CSA M81

Product Highlights

Southwire's 5KV HVTC is a CSA approved copper tape shielded cable for Industrial and Commercial medium voltage applications. FT4, -40°C, and 105°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. For use in cable trays, exposed run and hazardous locations as per the limitations in the Canadian Electrical Code Part I, particularly Table 19.

Construction

Conductor

  • Class B - compact stranded -8000 Series Aluminum -ACM

Options

  • Class B compact stranded copper
  • Class B compressed stranded copper
  • Strand blocking technology
  • Tinning on copper conductors

Conductor Shield

  • Extruded semi-conducting thermosetting polymeric layer

Insulation

  • TR-XLPE - (Tree Retardant Cross Linked Polyethylene)
  • Thickness: 0.115 inches (2.92mm) - nominal
  • Insulation level: 100% - grounded system
  • 105°C rated

Insulation Shield

  • Extruded Semi-conducting thermosetting polymeric layer
  • CSA 68.10 - Shield Removal/termination requirements are printed on the surface
  • Meets requirement of ICEA but built to CSA standards

Copper Tape Shield

  • Helically wrapped 5 mil copper tape with 25% overlap
  • Not designed to carry ground fault current
  • A separate bonding/grounding conductor may be required

Overall Jacket

  • Black PVC (optional colours available)
  • Nominal Thickness:
    No.2 AWG to No.1/0 AWG = 0.06 inches (1.52mm)
    No.2/0 AWG to 1000 kcmil = 0.08 inches (2.03mm)

Typical Print Legend

  • (CSA) SOUTHWIRE (NESC) #P# [#AWG or #kcmil] CPT ALL 115
    TRXLPE 8KV 100% INS LEVEL 25% TS SUN RES TC-ER 105° FT4
    (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]

HVTC AL 1C 140EPR TS PVC 8KV 133% CSA D86

Product Highlights

Southwire's 5KV HVTC is a CSA approved copper tape shielded cable for Industrial and Commercial medium voltage applications. FT4, -40°C, and 105°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. For use in cable trays, exposed run and hazardous locations as per the limitations in the Canadian Electrical Code Part I, particularly Table 19.

Construction

Conductor

  • Class B - compact stranded -8000 Series Aluminum -ACM

Options

  • Class B compact stranded copper
  • Class B compressed stranded copper
  • Strand blocking technology
  • Tinning on copper conductors

Conductor Shield

  • Extruded semi-conducting thermosetting polymeric layer

Insulation

  • No-lead EPR (Ethylene Propylene Rubber)
  • Thickness: 0.14 inches (3.56mm) - nominal
  • Insulation level: 133%
  • 105°C rated

Insulation Shield

  • Extruded Semi-conducting thermosetting polymeric layer
  • CSA 68.10 - Shield Removal/termination requirements are printed on the surface
  • Meets requirement of ICEA but built to CSA standards

Copper Tape Shield

  • Helically wrapped 5 mil copper tape with 25% overlap
  • Not designed to carry ground fault current
  • A separate bonding/grounding conductor may be required

Overall Jacket

  • Black PVC (optional colours available)
  • Nominal Thickness:
    No.2 AWG = 0.06 inches (1.52mm)
    No.1 AWG to 1000 kcmil = 0.08 inches (2.03mm)

Typical Print Legend

  • (CSA) SOUTHWIRE (NESC) #P# [#AWG or #kcmil] CPT ALL 140 EPR
    8KV 133% INS LEVEL 25% TS SUN RES TC-ER 105° FT4 (-40°C)
    LTGG RoHS YEAR [SEQUENTIAL METER MARKS]

More Products


CSA HVTC 15kV Tray Cables

More Products


HVTC CU 3C 220TRXLPE TS PVC 15KV 133% CSA U33

CSA Approvals

  • TC-ER – Tray Cable – Exposed Run rating
  • C22.2 No. 230 – Tray Cable Standard
  • C68.10 MV Shielded Power Cable Standard
  • SUN RES. - Sunlight Resistant
  • FT4 Flame Test
  • -40ºC low temperature rating
  • +105ºC high temperature rating

Designed for harsh Canadian environments

Applications

Southwire's 5KV HVTC is a CSA approved copper tape shielded cable for Industrial and Commercial medium voltage applications. FT4, -40°C, and 105°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. For use in cable trays, exposed run and hazardous locations as per the limitations in the Canadian Electrical Code Part I, particularly Table 19.

Construction

Conductor

  • Class B compressed stranded copper
    - in accordance with ASTM 83 and ASTM B8

Options

  • Class B compact stranded 8000 Series Aluminum -ACM
  • Class B compact stranded copper

Conductor Shield

  • Extruded semi-conducting thermosetting polymeric layer

Insulation

  • TR-XLPE - (Tree Retardant Cross Linked Polyethylene)
  • Thickness: 0.22 inches (5.59mm) - nominal
  • Insulation level: 133%
  • 105°C rated

Insulation Shield

  • Extruded Semi-conducting thermosetting polymeric layer
  • CSA 68.10 - Shield Removal/termination requirements are printed on the surface
  • Phase identification as per ICEA Method 3, using printed circuit numbers
  • Meets requirement of ICEA but built to CSA standards

Copper Tape Shield

  • Helically wrapped 5 mil copper tape with 25% overlap

Bonding Conductor

  • Class B compressed stranded bare copper
    - in accordance with ASTM B3 and B8

Fillers

  • Non-wicking, non-hygroscopic

Overall Jacket

  • Red PVC (optional colours available)
  • Nominal Thickness:
    No.2 AWG to 250 kcmil = 0.11 inches (2.79mm)
    350 kcmil to 750 kcmil = 0.14 inches (3.56mm)

Typical Print Legend

  • (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 220
    TRXLPE 5KV 133% INS LEVEL 25% TS SUN RES TC-ER 105° FT4
    (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]

HVTC CU 3C 220EPR TS PVC 15KV 133% CSA F70

CSA Approvals

  • TC-ER – Tray Cable – Exposed Run rating
  • C22.2 No. 230 – Tray Cable Standard
  • C68.10 MV Shielded Power Cable Standard
  • SUN RES. - Sunlight Resistant
  • FT4 Flame Test
  • -40ºC low temperature rating
  • +105ºC high temperature rating

Designed for harsh Canadian environments

Applications

Southwire's 5KV HVTC is a CSA approved copper tape shielded cable for Industrial and Commercial medium voltage applications. FT4, -40°C, and 105°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. For use in cable trays, exposed run and hazardous locations as per the limitations in the Canadian Electrical Code Part I, particularly Table 19.

Construction

Conductor

  • Class B compressed stranded copper
    - in accordance with ASTM 83 and ASTM B8

Options

  • Class B compact stranded 8000 Series Aluminum -ACM
  • Class B compact stranded copper

Conductor Shield

  • Extruded semi-conducting thermosetting polymeric layer

Insulation

  • No-lead EPR (Ethylene Propylene Rubber)
  • Thickness: 0.22 inches (5.59mm) - nominal
  • Insulation level: 133%
  • 105°C rated

Insulation Shield

  • Extruded Semi-conducting thermosetting polymeric layer
  • CSA 68.10 - Shield Removal/termination requirements are printed on the surface
  • Phase identification as per ICEA Method 3, using printed circuit numbers
  • Meets requirement of ICEA but built to CSA standards

Copper Tape Shield

  • Helically wrapped 5 mil copper tape with 25% overlap

Bonding Conductor

  • Class B compressed stranded bare copper
    - in accordance with ASTM B3 and B8

Fillers

  • Non-wicking, non-hygroscopic

Overall Jacket

  • Red PVC (optional colours available)
  • Nominal Thickness:
    No.2 AWG to 250 kcmil = 0.11 inches (2.79mm)
    350 kcmil to 750 kcmil = 0.14 inches (3.56mm)

Typical Print Legend

  • (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 220 EPR
    15KV 133% INS LEVEL 25% TS SUN RES TC-ER 105° FT4 (-40°C)
    LTGG RoHS YEAR [SEQUENTIAL METER MARKS]

HVTC CU 3C 175TRXLPE TS PVC 15KV 100% CSA V96

CSA Approvals

  • TC-ER – Tray Cable – Exposed Run rating
  • C22.2 No. 230 – Tray Cable Standard
  • C68.10 MV Shielded Power Cable Standard
  • SUN RES. - Sunlight Resistant
  • FT4 Flame Test
  • -40ºC low temperature rating
  • +105ºC high temperature rating

Designed for harsh Canadian environments

Applications

Southwire's 5KV HVTC is a CSA approved copper tape shielded cable for Industrial and Commercial medium voltage applications. FT4, -40°C, and 105°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. For use in cable trays, exposed run and hazardous locations as per the limitations in the Canadian Electrical Code Part I, particularly Table 19.

Construction

Conductor

  • Class B compressed stranded copper
    - in accordance with ASTM 83 and ASTM B8

Options

  • Class B compact stranded 8000 Series Aluminum -ACM
  • Class B compact stranded copper

Conductor Shield

  • Extruded semi-conducting thermosetting polymeric layer

Insulation

  • TR-XLPE - (Tree Retardant Cross Linked Polyethylene)
  • Thickness: 0.175 inches (4.45mm) - nominal
  • Insulation level: 100% - grounded system
  • 105°C rated

Insulation Shield

  • Extruded Semi-conducting thermosetting polymeric layer
  • CSA 68.10 - Shield Removal/termination requirements are printed on the surface
  • Phase identification as per ICEA Method 3, using printed circuit numbers
  • Meets requirement of ICEA but built to CSA standards

Copper Tape Shield

  • Helically wrapped 5 mil copper tape with 25% overlap

Bonding Conductor

  • Class B compressed stranded bare copper
    - in accordance with ASTM B3 and B8

Fillers

  • Non-wicking, non-hygroscopic

Overall Jacket

  • Red PVC (optional colours available)
  • Nominal Thickness:
    No.2 AWG to 350 kcmil = 0.11 inches (2.79mm)
    500 kcmil to 750 kcmil = 0.14 inches (3.56mm)

Typical Print Legend

  • (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 175
    TRXLPE 5KV 100% INS LEVEL 25% TS SUN RES TC-ER 105° FT4
    (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]

More Products


CSA HVTC 25kV Tray Cables

More Products


HVTC AL 1C 260EPR TS PVC 25KV 100% CSA J77

CSA Approvals

  • TC-ER – Tray Cable – Exposed Run rating
  • C22.2 No. 230 – Tray Cable Standard
  • C68.10 MV Shielded Power Cable Standard
  • SUN RES. - Sunlight Resistant
  • FT4 Flame Test
  • -40ºC low temperature rating
  • +105ºC high temperature rating

Designed for harsh Canadian environments

Applications

Southwire's 5KV HVTC is a CSA approved copper tape shielded cable for Industrial and Commercial medium voltage applications. FT4, -40°C, and 105°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. For use in cable trays, exposed run and hazardous locations as per the limitations in the Canadian Electrical Code Part I, particularly Table 19.

Construction

Conductor

  • Class B - compact stranded -8000 Series Aluminum -ACM

Options

  • Class B compact stranded copper
  • Class B compressed stranded copper
  • Strand blocking technology
  • Tinning on copper conductors

Conductor Shield

  • Extruded semi-conducting thermosetting polymeric layer

Insulation

  • No-lead EPR (Ethylene Propylene Rubber)
  • Thickness: 0.26 inches (6.60mm) - nominal
  • Insulation level: 100% - grounded system
  • 105°C rated

Insulation Shield

  • Extruded Semi-conducting thermosetting polymeric layer
  • CSA 68.10 - Shield Removal/termination requirements are printed on the surface
  • Meets requirement of ICEA but built to CSA standards

Copper Tape Shield

  • Helically wrapped 5 mil copper tape with 25% overlap
  • Not designed to carry ground fault current
  • A separate bonding/grounding conductor may be required

Overall Jacket

  • Black PVC (optional colours available)
  • Nominal Thickness:
    No.1 AWG to 500 kcmil = 0.08 inches (2.03mm)
    750 kcmil AWG to 1000 kcmil = 0.11 inches (2.79mm)

Typical Print Legend

  • (CSA) SOUTHWIRE (NESC) #P# [#AWG or #kcmil] CPT AL 260 EPR
    25KV 100% INS LEVEL 25% TS SUN RES TC-ER 105° FT4 (-40°C)
    TGG RoHS YEAR [SEQUENTIAL METER MARKS]

HVTC AL 1C 320EPR TS PVC 25KV 133% CSA B79

CSA Approvals

  • TC-ER – Tray Cable – Exposed Run rating
  • C22.2 No. 230 – Tray Cable Standard
  • C68.10 MV Shielded Power Cable Standard
  • SUN RES. - Sunlight Resistant
  • FT4 Flame Test
  • -40ºC low temperature rating
  • +105ºC high temperature rating

Designed for harsh Canadian environments

Applications

Southwire's 5KV HVTC is a CSA approved copper tape shielded cable for Industrial and Commercial medium voltage applications. FT4, -40°C, and 105°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. For use in cable trays, exposed run and hazardous locations as per the limitations in the Canadian Electrical Code Part I, particularly Table 19.

Construction

Conductor

  • Class B - compact stranded -8000 Series Aluminum -ACM

Options

  • Class B compact stranded copper
  • Class B compressed stranded copper
  • Strand blocking technology
  • Tinning on copper conductors

Conductor Shield

  • Extruded semi-conducting thermosetting polymeric layer

Insulation

  • No-lead EPR (Ethylene Propylene Rubber)
  • Thickness: 0.32 inches (8.13mm) - nominal
  • Insulation level: 133%
  • 105°C rated

Insulation Shield

  • Extruded Semi-conducting thermosetting polymeric layer
  • CSA 68.10 - Shield Removal/termination requirements are printed on the surface
  • Meets requirement of ICEA but built to CSA standards

Copper Tape Shield

  • Helically wrapped 5 mil copper tape with 25% overlap
  • Not designed to carry ground fault current
  • A separate bonding/grounding conductor may be required

Overall Jacket

  • Black PVC (optional colours available)
  • Nominal Thickness:
    No.1 AWG to 350 kcmil = 0.08 inches (2.03mm)
    500 kcmil to 1000 kcmil = 0.11 inches (2.79mm)

Typical Print Legend

  • (CSA) SOUTHWIRE (NESC) #P# [#AWG or #kcmil] CPT AL 320 EPR
    25KV 133% INS LEVEL 25% TS SUN RES TC-ER 105° FT4 (-40°C)
    LTGG RoHS YEAR [SEQUENTIAL METER MARKS]

HVTC AL 1C 260TRXLPE TS PVC 25KV 100% CSA V13

CSA Approvals

  • TC-ER – Tray Cable – Exposed Run rating
  • C22.2 No. 230 – Tray Cable Standard
  • C68.10 MV Shielded Power Cable Standard
  • SUN RES. - Sunlight Resistant
  • FT4 Flame Test
  • -40ºC low temperature rating
  • +105ºC high temperature rating

Designed for harsh Canadian environments

Applications

Southwire's 5KV HVTC is a CSA approved copper tape shielded cable for Industrial and Commercial medium voltage applications. FT4, -40°C, and 105°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, continuous rigid cable supports and concrete encaseable. For use in cable trays, exposed run and hazardous locations as per the limitations in the Canadian Electrical Code Part I, particularly Table 19.

Construction

Conductor

  • Class B - compact stranded -8000 Series Aluminum -ACM

Options

  • Class B compact stranded copper
  • Class B compressed stranded copper
  • Strand blocking technology
  • Tinning on copper conductors

Conductor Shield

  • Extruded semi-conducting thermosetting polymeric layer

Insulation

  • TR-XLPE - (Tree Retardant Cross Linked Polyethylene)
  • Thickness: 0.26 inches (6.60mm) - nominal
  • Insulation level: 100% - grounded system
  • 105°C rated

Insulation Shield

  • Extruded Semi-conducting thermosetting polymeric layer
  • CSA 68.10 - Shield Removal/termination requirements are printed on the surface
  • Meets requirement of ICEA but built to CSA standards

Copper Tape Shield

  • Helically wrapped 5 mil copper tape with 25% overlap
  • Not designed to carry ground fault current
  • A separate bonding/grounding conductor may be required

Overall Jacket

  • Black PVC (optional colours available)
  • Nominal Thickness:
    No.1 AWG to 500 kcmil = 0.08 inches (2.03mm)
    750 kcmil to 1000 kcmil = 0.11 inches (2.79mm)

Typical Print Legend

  • (CSA) SOUTHWIRE (NESC) #P# [#AWG or #kcmil] CPT AL 260
    TRXLPE 25KV 100% INS LEVEL 25% TS SUN RES TC-ER 105° FT4
    (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]

More Products


©2018. F S INTL. AND INDUSTRIAL CORP.
Site design and maintenance by Watta Studio.